KDIP Supreme
Key Facts
- No water vapor can penetrate as ALUGLASS achieves zero water vapor permeability.
- KDIP can be used with no additional requirement of handling and weather protection such as application of canvas + vapor barrier.
- KDIP is rot proof, resists the effects of moisture and will not decompose through continual exposure to the elements.
- KDIP will not shrink due to the age or temperature variations.
- KDIP will maintain its thermal properties throughout the lifetime of the construction.
- KDIP is compatible to direct painting. It is recommended to use only anti-fungal and antibacterial paints on KDIP in areas where services are exposed like malls, exhibition center etc. for aesthetic finish. This will save costly metallic cladding
Product description
KDIP Supreme is manufactured from stable glass fibers bonded with thermo-setting resins, in the form of blanket or rigid boards with factory applied ALUGLASS (aluminium foil /glass fabric laminate) facing as vapor barrier. KDIP has a high resistance to accidental damage from knocks and handling during installation and maintenance. The product is dimensionally stable under varying conditions of temperature and humidity, it is rot proof, odourless, non-hygroscopic and will not sustain vermin and fungus. It is Easy to clean.
SILENT FEATURES
- KDIP is faced with factory applied ALUGLASS facing.
- KDIP can be used with no additional requirement of handling and weather protection such as application of canvas + vapor barrier
- ALUGLASS is aluminum foil laminated with glass fabric.
- It has extremely high bursting strength of 270 psi i.e. 3-4 times higher than that of conventional facings.
- It has extremely high tensile strength of 14.5 KN/m i.e. 3-4 times higher than that of conventional facings.
- ALUGLASS has high mechanical strength and durability
FIRE SAFETY
Fibers are non combustible when tested in accordance with BS 476 (part 4), ASTM E 136, KDIP achieves Class 1 when tested as per BS 476 (Part 7). IS01182 ALUGLASS facing achieves Class 0 when tested as per BS 476 (Part 6 and Part 7). Flame spread: Not over 25 and Smoke developed: Not over 50. When tested in accordance with ASTM E 84.
Technical description
Characteristic |
Symbol |
Unit |
Quantities and measured values |
Standard |
|
---|---|---|---|---|---|
Thermal Conductivity |
T |
(°C) |
25 |
ASTM C518 |
|
l |
( W /m·K ) |
0.033 |
|||
Density |
Rolls |
ρ |
(kg/m3) |
32 (Tolerance: ± 15%) |
ASTM C167 |
Dimensions |
L, W, T |
(m) |
(6.0 – 36.0), (1.2), (0.012 – 0.075) |
||
Density |
Slab/Boards |
ρ |
(kg/m3) |
32 (Tolerance: ± 15%) |
ASTM C303 |
Dimensions |
L, W, T |
(m) |
(1.0 - 2.4), (1.2), (0.013 – 0.150) |
||
Facing |
Faced with Aluglass |
||||
Reaction to Fire Class (Unfaced) |
Euro-class A1 Non-combustible |
EN 13501-1 ASTM E136 |
|||
Surface Burning Characteristics -Flame Spread Index -Smoke Developed Index |
≤ 25 ≤ 50 |
ASTM E84 |
|||
Water Vapour Sorption |
(%) |
< 1 (by volume) |
ASTM C1104 |
||
Maximum Service Temperature Min. Max. (Fiber) Max. (Facing) |
°C |
-50 +232 +100 |
ASTM C411 |
||
Fungi Resistance |
Do not promote fungi growth |
ASTM C1338 |
|||
Stress Corrosion to Austenitic Stainless Steel. |
No Cracking observed |
ASTM C871 |
|||
Corrosiveness to Steel |
No Corrosion |
ASTM C665 |
|||
Ozone Depletion Potential (ODP) |
‘0’ |
- |
|||
Global Warming Potential (GWP) |
<5 |
- |
|||
Rigidity |
Semi-Rigid/Flexible |
ASTM C1101 |
|||
Standard Compliance |
ASTM C612 Type IA & IB ASTM C553, ASTM C665 |
Product variations
Name | Density [kg/m3] | Facing | Thml resistance | Packaging (Roll) | Thickness (mm) | Width (m) | Lenght (m) |
---|---|---|---|---|---|---|---|
NameKDIP Supreme | Density [kg/m3]32 | FacingAluglass | Thml resistance0.76 | Packaging (Roll)1 | Thickness (mm)25 | Width (m)1.2 | Lenght (m)20 |
NameKDIP Supreme | Density [kg/m3]32 | FacingAluglass | Thml resistance1.52 | Packaging (Roll)1 | Thickness (mm)50 | Width (m)1.2 | Lenght (m)10 |
Other dimensions, and density are available on request